FuelClarity™ Specifications
|
Enclosure |
NEMA 4 UL 508 A Listed |
| 48” W X 36” H X 12” D – Dual Door |
| Keyed Lock |
Controls |
NEMA 4 UL 508 A Listed
(Optional NEMA Enclosures Available) |
Allen Bradley PLC Controller with MODBUS,
Ethernet Communications |
| Touch Screen Interface |
Audible and Visual Alarms for Filter Servicing, Water
Presence in Filter, and Leak Detection |
| Manual-Off-Auto Switch |
| Optional Controller Heater |
| Day of Week/Time of Day / Duration |
Pump |
Closed Coupled Rotary Gear Pump |
| Optional Flow Rates Available |
| Pump Housing and Gears are Made of Top Quality Bronze |
Pump Motor – 1.5 hp, 1750 rpm, Single Phase,
60Hz, 110/220 VAC |
Filtration |
Stage I – 10 Micron |
| Stage II – 1 Micron/Water Removal |
| Optional Filtration Levels Available |
Standard Features |
Differential Pressure Sensors Across Fuel Filters to
Determine Filter Service |
| Optical Liquid Level Sensors to Detect System Leak |
| Water Sensing Probe in Filter(s) to Detect the Presence of Water that Accumulates in the Bottom of the Bowl |